Presentation |
A highly efficient, modular, 500 kVA scalable to 1000 kVA 3-phase UPS that provides the performance, flexibility, and maximized asset utilization today’s large data centers and mission critical applications require. This EcoStruxure Ready UPS features up to 99% efficiency with patented ECOnversion technology. Includes 5×8 start-up service.
|
|
---|---|---|
Lead time |
Special Order – Call for Quoted Lead Times
|
provided equipment |
Installation guide
Start-up service |
|
---|---|---|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
|
UPS size |
WS
|
colour |
White
|
|
---|---|---|
depth |
90 cm
|
|
height |
197 cm
|
|
mounting preference |
No preference
|
|
net weight |
2030 kg
|
|
mounting mode |
Not rack-mountable
|
|
two post mountable |
0
|
|
USB compatible |
No
|
|
width |
240 cm
|
network frequency |
40…70 Hz
|
|
---|---|---|
Input voltage |
380 V
415 V 440 V |
|
maximum input current |
851 A
|
|
max short time withstand current |
100 kA
|
|
input harmonic distortion |
Less than 3 % for full load
|
|
input voltage |
400 V 3 phases
|
|
load power factor |
From 0.7 leading to 0.5 lagging without any derating
|
rated power in W |
500000 W
|
|
---|---|---|
Maximum configurable power in W |
1000000 W
|
|
output frequency |
50 Hz sync to mains
60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
|
Output voltage |
380 V
415 V 440 V |
|
crest factor |
3 with THC <5%
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
output harmonic distortion |
< 2% linear load and < 3% non-linear load
|
|
output overload operation |
10 minutes at 125% and 60 seconds at 150%
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0063
|
|
curve load maximum |
100 %
|
|
curve load minimum |
1 %
|
|
curve proportional loss |
0.0042
|
|
curve square loss |
0.038
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with 400V/50Hz electrical input and balanced resistive load (PF =
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
graph display |
1
|
|
output voltage |
400 V 3 phases
|
|
Maximum configurable power in VA |
1000000 VA
|
|
rated power in VA |
500000 VA
|
product certifications |
cUL listed
C-Tick CE UL 1778 5th edition |
|
---|---|---|
standards |
IBC 2012
IEC 62040-1-1 IEC 62040-2 IEC 62040-3 IEC 62040-4 ISTA 2B |
ambient air temperature for operation |
0…40 °C
|
|
---|---|---|
relative humidity |
0…95 % non-condensing
|
|
operating altitude |
0…3333 ft
|
|
ambient air temperature for storage |
-15…40 °C
|
|
storage Relative Humidity |
0…95 % Non-condensing
|
|
storage altitude |
0.00…15240.00 m
|
|
acoustic level |
69.5 dBA
|
|
heat dissipation |
80387 Btu/h
|
|
show note OP temperature |
No
|
|
IP degree of protection |
IP20
|
battery type |
External battery system
|
|
---|---|---|
liquid value |
0
|
|
battery voltage |
480 V
|
|
discharge battery voltage |
384 V DC
|
|
battery curve |
B
|
|
Battery power in VAH |
0 VAh runtime
|
|
extended runtime |
0
|
free slots |
2
|
|
---|---|---|
control panel |
7″ touch screen display
|
|
alarm |
Audible and visible alarms prioritized by severity
|
Package 1 Weight |
2592 kg
|
|
---|---|---|
Package 1 Height |
215 cm
|
|
Package 1 width |
317 cm
|
|
Package 1 Length |
106 cm
|
Warranty |
1 year on-site repair or replace with factory authorized Start-Up
|
---|