Presentation |
High performance, compact 3 phase UPS power protection fully standardized for heavy industrial applications and harsh environments. Available in 3:3 and 3:1 configurations.
|
|
---|---|---|
Lead time |
Usually Ships within 6 Weeks
|
rated power in W |
8000 W
|
|
---|---|---|
rated power in VA |
10000 VA
|
|
output connector type |
Hard wire 5-wire (3P + N + E) 1
|
|
Main Output Voltage |
400 V 3 phases
|
|
Other Output Voltage |
400 V
|
|
Main Input Voltage |
400 V 3 phases
|
provided equipment |
Dust filter
Installation guide Network management card Parallel card Relay board User manual |
|
---|---|---|
bypass wiring configuration |
5 wire (3P + N + E)
|
|
bypass voltage tolerance |
+/- 10 %
|
|
max bypass input current |
16 A
|
|
bypass current protection |
25 A
|
|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
colour |
Light grey
|
|
---|---|---|
depth |
80 cm
|
|
height |
210 cm
|
|
mounting preference |
No preference
|
|
net weight |
310 kg
|
|
mounting mode |
Not rack-mountable
|
|
two post mountable |
0
|
|
USB compatible |
No
|
|
width |
60 cm
|
network frequency |
45…65 Hz
|
|
---|---|---|
number of input connectors |
1 hard wire 5-wire (3P + N + E)
|
|
input voltage limits |
360…440 V 400 V
|
|
maximum input current |
23 A
|
|
switching current capacity |
32 A
|
|
max short time withstand current |
65 kA
|
|
input harmonic distortion |
Less than 5 % for full load
|
|
input protection type |
Upstream protection according to source
|
|
input current |
23 A per phase (3 phases)
|
|
load power factor |
0.5 leading to 0.5 lagging without derating
|
|
Input Power Factor at Full Load |
0.96
|
Maximum configurable power in W |
8000 W
|
|
---|---|---|
harmonic distortion |
Less than 5 %
|
|
output frequency |
50/60 Hz +/- 1 Hz sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
|
crest factor |
Unlimited
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
output voltage tolerance |
+/- 1 %
|
|
output harmonic distortion |
< 2% at 100% linear load and < 5% at 100% non-linear load
|
|
output overload operation |
10 minutes at 125% and 60 seconds at 150%
|
|
required output current protection |
25 A
|
|
neutral output current |
14 A
|
|
bypass type |
Built-in bypass
|
|
efficiency |
93.3 % (full load)
93.6 % (half load) 92.8 % (in battery operation) |
|
Maximum configurable power in VA |
10000 VA
|
product certifications |
CE
|
|
---|---|---|
marking |
CE Mark
|
|
standards |
IBC 2012
IEC 62040-1-1 IEC 62040-2 IEC 62040-3 ISTA 2B VFI-SS-111 |
ambient air temperature for operation |
-10…40 °C
|
|
---|---|---|
relative humidity |
0…95 % non-condensing
|
|
operating altitude |
0…10000 ft
|
|
ambient air temperature for storage |
-15…40 °C
|
|
storage Relative Humidity |
0…95 % Non-condensing
|
|
storage altitude |
0.00…4572.00 m
|
|
acoustic level |
65 dBA
|
|
heat dissipation |
1963 Btu/h
|
|
IP degree of protection |
IP42 with air filter
|
battery type |
External battery system
|
|
---|---|---|
number of battery filled slots |
0
|
|
number of battery free slots |
0
|
|
max current discharge |
26.2 A
|
|
Battery power in VAH |
0 VAh runtime
|
|
extended runtime |
0
|
free slots |
1
|
|
---|---|---|
preinstalled device |
Network management card 2 with environmental monitoring, out of band access and Modbus
|
|
control panel |
Multifunction LCD status and control console
|
|
alarm |
Audible and visible alarms prioritized by severity
|
|
Emergency power off |
Yes
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
357.74 kg
|
|
Package 1 Height |
230 cm
|
|
Package 1 width |
82 cm
|
|
Package 1 Length |
108.2 cm
|
Warranty |
1 year on-site repair or replace with factory authorized Start-Up
|
---|