General Features
● 138-485 Vac wide input voltage range to minimize battery use
● High input power factor up to 0.99
● 3-level topology design, efficiency is up to 96.5%
● Support parallel expanded operation:maximum is 8 units
● Smart sleeping mode for energy saving and prolong the life time of the system
● User-friendly 7-inch and 10-inch LCD touch screen for easy UPS operation
Technical Specification
| Module Model | HPM3300E-RM-50 | |||||||
| Cabinet Model | HPM3300E-200 | HPM3300E-300 | HPM3300E-400 | HPM3300E-500 | HPM3300E-600 | HPM3300E-800 | HPM3300E-1000 | |
| Cabinet capacity (VA) | 200k | 300k | 400k | 500k | 600k | 800k | 1000k | |
| Module capacity (VA) | 50k | |||||||
| Max. number | 4 | 6 | 8 | 10 | 12 | 16 | 20 | |
| INPUT | ||||||||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||
| Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for 100% Load; | |||||||
| Operating frequency range | 40Hz-70Hz | |||||||
| Power factor | ≥0.99 | |||||||
| Harmonic distortion (THDi) | ≤3% (100% linear load) | |||||||
| Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | |||||||
| Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | ||||||||
| Bypass frequency tracking range | ±10% | |||||||
| Power Walk In | Support | |||||||
| Generator input | Support | |||||||
| OUTPUT | ||||||||
| Rated voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||
| Power factor | 1 | |||||||
| Voltage regulation | ±1% | |||||||
| Output | Line mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | ||||||
| frequency | Bat. mode | (50/60±0.1%)Hz | ||||||
| Crest factor | 3 :1 | |||||||
| Harmonic distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load | |||||||
| Efficiency | up to 96.5% | |||||||
| BATTERY | ||||||||
| Battery voltage | VRLA battery | 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) | ||||||
| Lithium battery | 512Vdc | |||||||
| Power module charge current | 20A (Max.) | |||||||
| SYSTEM FEATURES | ||||||||
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | |||||||
| Overload | Line mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately | ||||||
| Bypass mode | 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms | |||||||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||||
| Low battery voltage | Alarm and Switch off | |||||||
| Self-diagnostics | Upon Power On and Software Control | |||||||
| Backfeed protection | Support | |||||||
| EPO (optional) | Shut down UPS immediately (turn to bypass optional) | |||||||
| Battery | Advanced Battery Management | |||||||
| Noise suppression | Complies with EN62040-3 | |||||||
| Audible & visual alarms | Line Failure, Battery Low, Overload, System Fault | |||||||
| Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | |||||||
| Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | |||||||
| Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | |||||||
| ENVIRONMENTAL | ||||||||
| Operating temperature | 0℃~40℃ | |||||||
| Storage temperature | -25℃~55℃ | |||||||
| Humidity range | 0~95% (non condensing) | |||||||
| Altitude | <1500m, derating required when >1500m | |||||||
| Noise level | <65dB | <66dB | <68dB | <70dB | <73dB | |||
| PHYSICAL | ||||||||
| Dimension | UPS cabinet (S) | 600×850×2000 | 600×850×2000 | 1200×850×2000 | 2000×850×2000 | |||
| UPS cabinet (F) | 1200×850×2000 | |||||||
| Power module | 440×620×130 | |||||||
| UPS cabinet | 270 | 290 | 310/470 | 650 | 720 | 980 | 1080 | |
| Net weight (kg) | Power module | 34 | ||||||
| STANDARDS | ||||||||
| Safety | IEC/EN62040-1, IEC/EN62477-1 | |||||||
| EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) | |||||||
| Module Model | HPM3300E-RM-60 | ||||||
| Cabinet Model | HPM3300E-300 | HPM3300E-480 | HPM3300E-600 | HPM3300E-840 | HPM3300E-1080 | HPM3300E-1200 | |
| Cabinet capacity (VA) | 300k | 480k | 600k | 840k | 1080k | 1200k | |
| Module capacity (VA) | 60K | ||||||
| Max. number | 5 | 8 | 10 | 14 | 18 | 20 | |
| INPUT | |||||||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | ||||||
| Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for 100% Load; | ||||||
| Operating freque | 40Hz-70Hz | ||||||
| Power factor | ≥0.99 | ||||||
| Harmonic distortion (THDi) | ≤3% (100% linear load) | ||||||
| Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | ||||||
| Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | |||||||
| Bypass frequency tracking range | ±10% | ||||||
| Power Walk In | Support | ||||||
| Generator input | Support | ||||||
| OUTPUT | |||||||
| Rated voltage | 380/400/415Vac, (3Ph+N+PE) | ||||||
| Power factor | 1 | ||||||
| Voltage regulation | ±1% | ||||||
| Output | Line mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | |||||
| frequency | Bat. mode | (50/60±0.1%)Hz | |||||
| Crest factor | 3 : 1 | ||||||
| Harmonic distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load | ||||||
| Efficiency | up to 96.5% | ||||||
| BATTERY | |||||||
| Battery voltage | VRLA battery | 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) | |||||
| Lithium battery | 512Vdc | ||||||
| Power module charge current | 20A (Max.) | ||||||
| SYSTEM FEATURES | |||||||
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||||||
| Overload | Line mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately | |||||
| Bypass mode | 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms | ||||||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | ||||||
| Low battery voltage | Alarm and Switch off | ||||||
| Self-diagnostics | Upon Power On and Software Control | ||||||
| Backfeed protection | Support | ||||||
| EPO (optional) | Shut down UPS immediately (turn to bypass optional) | ||||||
| Battery | Advanced Battery Management | ||||||
| Noise suppression | Complies with EN62040-3 | ||||||
| Audible & visual alarms | Line Failure, Battery Low, Overload, System Fault | ||||||
| Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | ||||||
| Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | ||||||
| Communication | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | ||||||
| ENVIRONMENTAL | |||||||
| Operating temperature | 0℃~40℃ | ||||||
| Storage temperature | -25℃~55℃ | ||||||
| Humidity range | 0~95% (non condensing) | ||||||
| Altitude | <1500m, derating required when >1500m | ||||||
| Noise level | <66dB | <70dB | <73dB | ||||
| PHYSICAL | |||||||
| Dimension | UPS cabinet (S) | 600×850×2000 | 1200×850×2000 | 2000×850×2000 | 2000×850×2000 | ||
| UPS cabinet (F) | |||||||
| Power module | 440×620×130 | ||||||
| UPS cabinet | 290 | 650 | 720 | 980 | 1080 | 1200 | |
| Net weight (kg) | Power module | 34 | |||||
| STANDARDS | |||||||
| Safety | IEC/EN62040-1, IEC/EN62477-1 | ||||||
| EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) | ||||||