Modular UPS-HPM Family (10-150kVA)

With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads.
The series’ N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and  has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.

General Features

● Modular design, including power module, bypass module, monitoring module, which means it can be easily integrated in MDC or customized cabinet.

● Flexible power module: 10/15/20/25/30kVA ((2U))

● High input power factor, it is up to 0.99.

● Width input voltage range:line voltage range is 138-485V, UPS would be derating when input voltage is below 305V.

● Parallel redundant configurations:failure of one module will not impact system or site operation.

● Three level topology design, efficiency is up to 95.8%.

● Sleeping Mode to save energy.

● Support parallel expanded operation: maximum is 6 units, Support sharing batteries for the UPS in parallel.

 

General Features

Module Model HPM3300E-RM-10
Cabinet Model HPM3300E-20 HPM3300E-40 HPM3300E-60
Cabinet capacity (VA) 10k~20k 10k~40k 10k~60k
Module capacity (VA) 10k
Max. Number 2 4 6
Module Model HPM3300E-RM-15
Cabinet Model HPM3300E-30 HPM3300E-60 HPM3300E-90
Cabinet capacity (VA) 15k~30k 15k~60k 15k~90k
Module capacity (VA) 15k
Max. Number 2 4 6
Module Model HPM3300E-RM-20
Cabinet Model HPM3300E-40 HPM3300E-80 HPM3300E-120
Cabinet capacity (VA) 20k~40k 20k~80k 20k~120k
Module capacity (VA) 20k
Max. Number 2 4 6
Module Model HPM3300E-RM-25
Cabinet Model HPM3300E-50 HPM3300E-100 HPM3300E-150
Cabinet capacity (VA) 25k~50k 25k~100k 25k~150k
Module capacity (VA) 25k
Max. Number 2 4 6
Module Model HPM3300E-RM-30
Cabinet Model HPM3300E-60 HPM3300E-120 HPM3300E-150
Cabinet capacity (VA) 30k~60k 30k~120k 30k~150k
Module capacity (VA) 30k
Max. Number 2 4 5+1
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range 40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) ≤3% (100% linear load)
Bypass voltage range Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency range Frequency protection range: ±10%
Power Walk In Support
Generator input Support
OUTPUT
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1.0
Voltage regulation ±1%
Output frequency Line Mode Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤1% with linear load; ≤3% with nonlinear load
Efficiency up to 95.8%
BATTERY
Battery voltage Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional);
360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)
Power module charge current 18A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line Mode ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately.
Bypass Mode 135% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Backfeed Support
EPO Shut down UPS immediately (turn to bypass optional)
Battery Advanced Battery Management
Noise suppression Complies with EN62040-3
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display Input, Output, Battery, Command, Setting, Maintenance
Communication interface RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude <1500m, derating required when >1500m
Noise level(from 1M distance) <58dB <60dB <62dB
PHYSICAL
Dimension              W×D×H (mm) UPS cabinet 485×850×353(8U) 485×850×575(13U) 485×850×752(17U)
Power module 440×620×86(2U)
Net weight (kg) UPS cabinet 69 79 98
Power module 10kVA: 19; 15~30kVA: 21
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)
Specifications are subject to change without prior notice.

Bestsellers

This product is already in quote request list.

UPS monitoring software-RUPS 2000

An effective UPS power monitoring software gives you critical insights on battery charge, performance and sends you alerts on critical.RUPS 2000 is such a UPS monitoring that continuously checks the status of system AC power and UPS battery condition. Conbined with ClientMate, RUPS 2000 could be as server software, helping CilentMates get  UPS status from RUPS 2000.  if any abnormal condition occures, it will send out warning message to inform user and shut down the system after a pre-setting delay time.  For example,RUPS 2000 notifies you of any power outages or imminent server shutdown in real time and reduces the risk of losing data due to events that cause major power failures. This permits faster resolution and handling of the network, server, and service outages. Download Now
This product is already in quote request list.
This product is already in quote request list.

Modular UPS-HPM Family (10-150kVA)

With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads. The series' N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and  has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.
This product is already in quote request list.
This product is already in quote request list.

GFM Series (100-3000Ah)

KSTAR valve regulated lead acid battery can prevent air from being absorbed into it, and at the same time it also can protect the battery from damage caused by gas emitting in the period of recharging. There is no emission of acid mist and electrolyte when the sealed battery is in floating condition. Meanwhile, the patented battery tray can match with the battery and it can protect the battery from the harm of electrolyte leakage.
This product is already in quote request list.
This product is already in quote request list.

Deep Cycle Series (38-2000Ah)

KSTAR valve regulated lead acid battery can prevent air from being absorbed into it, and at the same time it also can protect the battery from damage caused by gas emitting in the period of recharging .There is no emission of acid mist and electrolyte when the sealed battery is in floating condition. Meanwhile, the patented battery tray can match with the battery and it can protect the battery from the harm of electrolyte leakage.
This product is already in quote request list.
This product is already in quote request list.

Memopower Li 1-3kVA UPS with Lithium Batteries

The Memopower Li series online UPS with LiFePO4 Lithium Batteries features long service time and high density. With smart battery management system it can improve the overall performance of the UPS and lengthen the warranty. This Long-life-span lithium-ion UPS can also shift your refresh cycle to be in line with your IT equipment, saving time and money spent on labor and replacement batteries.
This product is already in quote request list.
This product is already in quote request list.

High Rate Series(230-2900W)

KSTAR valve regulated lead acid battery can prevent air from being absorbed into it, and at the same time it also can protect the battery from damage caused by gas emitting in the period of recharging. There is no emission of acid mist and electrolyte when the sealed battery is in floating condition. Meanwhile, the patented battery tray can match with the battery and it can protect the battery from the harm of electrolyte leakage.
This product is already in quote request list.
This product is already in quote request list.

HPM3300E-T Tower UPS with Lithium Batteries

HPM3300E-T series UPS is developed as a high frequency large capacity tower UPS which can solve most of the power supply problems, such as blackout, over-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference and frequency fluctuation. It has a strong load capacity and can be matched with full inductive load or capacitive load. The UPS can be used in various applications ranging from computer equipment, automatic equipment, large and medium-sized data centers, bank/security settlement centers, communication systems to industrial equipment.
This product is already in quote request list.

Product has been added to your cart