General Features
● True online double conversion design
● Build-in input and output transformer with strong galvanic isolation
● Wide input range, avoid frequently transfer to battery mode, prolong the battery lifetime
● Intelligent battery management technology, fully protect battery
● Battery cold start function
● Comprehensive and reliable protection
● User-friendly network management
Technical Specification
| MODEL | UIC60L | UIC80L | UIC100L | UIC150L | UIC200L | UIC300L | UIC400L | |||
| Capacity (VA/Watts) |
6kVA/4.8kW | 8kVA/6.4kW | 10kVA/8kW | 15kVA/12kW | 20kVA/16kW | 30kVA/24kW | 40kVA/32kW | |||
| INPUT | ||||||||||
| Operating voltage range |
380Vac(±20%), (3Ph+N+PE) | |||||||||
| Operating frequency range |
50/60Hz(±5%) | |||||||||
| Power Factor | >0.97 (with filter) | |||||||||
| Max. input current (A) |
14 | 18 | 23 | 34 | 45 | 68 | 90 | |||
| OUTPUT | ||||||||||
| Output Voltage | 220Vac(±0.5%) / 230Vac(±0.5%) | |||||||||
| Output frequency |
50/60Hz(±0.5%) | |||||||||
| Efficiency | 6~8KVA: 85% online 10~40KVA: 90% online | |||||||||
| Harmonic Distortion (THDv) |
<1.5% with linear load | |||||||||
| Crest factor | 3:1 (max) | |||||||||
| BATTERY | ||||||||||
| Battery voltage | 192Vdc | 240Vdc | ||||||||
| SYSTEM FEATURES | ||||||||||
| Transfer time | 0ms (Line mode →Battery mode) | |||||||||
| Overload | ≤125% /1min, ≤150% /200ms,to Bypass | |||||||||
| LED display | Battery low, Mains status, Inverter, Bypass, UPS failure, Overload | |||||||||
| LCD display | I/O voltage, Frequency, Battery voltage, Load percentage,Internal temperature | |||||||||
| Communication interface |
RS232, SNMP (optional), Dry contact(optional),RS485 | |||||||||
| ENVIRONMENT | ||||||||||
| Operating Temperature |
0℃~40℃ | |||||||||
| Storage temperature |
-25~55℃ | |||||||||
| Humidity range | 0~95% (non-condensing) | |||||||||
| Altitude | <1500m | |||||||||
| Noise level | <55dB | |||||||||
| PHYSICAL | ||||||||||
| Dimension W×D×H (mm) |
305×585×864 | 430×830×1100 | ||||||||
| Net Weight (S/H) (kg) |
100 | 110 | 120 | 145 | 155 | 255 | 280 | |||
| STANDARDS | ||||||||||
| Safety | IEC/EN62040-1; IEC/EN60950-1 | |||||||||
| EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 | |||||||||