General Features
● True double-conversion
● Rack-mounted and floor-standing tower can be convertible
● Patented Minic LCD of which content can be rotated according to the type of deployment
● DSP technology guarantees high reliability
● N+X parallel redundancy
● Selectable quantity of battery for each group:16/18/20 pieces
● Adjustable charging current via LCD
● 3-stage charging design optimizes battery performance
● ECO mode operation for energy saving
● Self-diagnosis at startup
● Emergency power off function(EPO)
● Maintenance bypass is convenient for maintenance
● Generator compatible
● PDU is convenient for connecting load
● Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
● Cold start
Technical Specification
| MODEL | UBR60L | UBR100L | ||
| Capacity (VA/Watts) | 6K / 5.4K | 10K / 9K | ||
| INPUT | ||||
| Nominal Voltage | 220/230/240Vac(L+N+PE) | |||
| Operating Voltage Range |
120Vac-276Vac | |||
| Operating Frequency Range |
50Hz:45~55Hz,60Hz:54~66Hz | |||
| Power Factor | ≥0.99 | |||
| Bypass Voltage Range | Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||
| 230V:+20%(Optional +10%,+15%) | ||||
| 240V:+15%(Optional +10% ) | ||||
| Min. voltage: -45% (Optional -20%,-30%) | ||||
| ECO Range | Same as bypass | |||
| Harmonic Distortion (THDi) |
≤5%(100% non-linear load) | |||
| OUTPUT | ||||
| Output Voltage | 220/230/240Vac | |||
| Power Factor | 0.9 | |||
| Voltage Regulation | ±1% | |||
| Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) | ||
| Bat. Mode | (50/60±0.1)Hz | |||
| Crest Factor | 3:1 | |||
| Harmonic Distortion (THDv) |
≤2% with linear load | |||
| ≤5% with non-linear load | ||||
| Waveform | Pure Sinewave | |||
| Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||
| EFFICIENCY | ||||
| Efficiency | Up to 94% | |||
| BATTERY | ||||
| Battery Voltage | Optional Voltage: ±96/108/120Vdc | |||
| Typical Recharge Time | 6-8 hours (To 90% capacity) | |||
| Charging Current | Maximum current 10A; | |||
| PROTECTION | ||||
| Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode | ||
| Bypass Mode | 40A(Input breaker) | 60A(Input breaker) | ||
| Short Circuit | Hold Whole System | |||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||
| Battery Low | Alarm and Switch off | |||
| INDICATORS | ||||
| Audible & Visual alarms |
Line Failure, Battery Low, Overload, System Fault | |||
| Status LED & LCD Display |
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault | |||
| Reading On The LCD Display |
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time |
|||
| MANAGEMENT | ||||
| Communication Interface |
RS232,USB, Parallel Port, SNMPcard(Optional), Relay card (Optional) | |||
| ENVIRONMENT | ||||
| Operating Temperature |
0℃~40℃ | |||
| Storage Temperature | -25℃~55℃ | |||
| Humidity Range | 0~95% (Non-condensing) | |||
| Altitude | < 1500m | |||
| Noise Level | <55dB | |||
| PHYSICAL | ||||
| Dimension W×D×H (mm) |
443×580×131 (3U) | |||
| Net Weight (kg) | 19 | 20 | ||
| STANDARDS | ||||
| Noise Suppression | Complies with EN62040-2 | |||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | |||
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||
| IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||
| BATTERY PACK | ||||
| Model | EXBR±120V | |||
| Battery type& Max.quantity |
7Ah×20/9Ah×20 | |||
| Dimensions W×D×H (mm) |
443×720×131 (3U) | |||
| Net Weight (kg) | 65/75 | |||