General Features
● True double-conversion
● DSP technology guarantees high reliability
● N+X parallel redundancy
● Compatible with three-phases and single-phase input
● Selectable quantity of battery for each group:16/18/20 pieces
● Adjustable charging current via LCD
● 3-stage charging design optimizes battery performance
● ECO mode operation for energy saving
● Self-diagnosis at startup
● Emergency power off function(EPO)
● Maintenance bypass is convenient for maintenance
● Generator compatible
● Communications:RS-232,USB,Parallel card(Optional),SNMP card(Optional), Relay card (Optional)
● Cold start
Technical Specification
| MODEL | UC100 | UC100L | UC150L | UC200L | ||
| Capacity (VA/Watts) | 10K / 9K | 15K / 13.5K | 20K / 18K | |||
| INPUT | ||||||
| Nominal Voltage | 380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE) | |||||
| Operating Voltage Range |
208~478Vac or 120VAC-276Vac | |||||
| Operating Frequency Range |
50Hz:45~55Hz,60Hz:54~66Hz | |||||
| Power Factor | ≥0.99 | |||||
| Bypass Voltage Range |
Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||||
| 230V:+20%(Optional +10%,+15%) | ||||||
| 240V:+15%(Optional +10% ) | ||||||
| Min. voltage: -45% (Optional -20%,-30%) | ||||||
| ECO Range | Same as bypass | |||||
| Harmonic Distortion (THDi) |
≤5%(100% non-linear load) | |||||
| OUTPUT | ||||||
| Rated Voltage | 220/230/240Vac | |||||
| Power Factor | 0.9 | |||||
| Voltage Regulation | ±1% | |||||
| Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) |
||||
| Bat. Mode | (50/60±0.1)Hz | |||||
| Crest Factor | 3:1 | |||||
| Harmonic Distortion (THD) |
≤2% with linear load | |||||
| ≤5% with non-linear load | ||||||
| Waveform | Pure Sinewave | |||||
| Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||||
| EFFICIENCY | ||||||
| Efficiency | Up to 94% | Up to 94.5% | ||||
| BATTERY | ||||||
| Battery Voltage | Selectable Voltage: ±96/108/120Vdc | |||||
| Typical Recharge Time |
6-8 hours (To 90% capacity) | |||||
| Charging Current | Maximum current 10A | |||||
| PROTECTION | ||||||
| Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode |
||||
| Bypass Mode | 63A(Input breaker) | 100A(Input breaker) | 125A(Input breaker) | |||
| Short Circuit | Hold Whole System | |||||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||
| Battery Low | Alarm and Switch off | |||||
| INDICATORS | ||||||
| Audible & Visual Alarms |
Line Failure, Battery Low, Overload, System Fault | |||||
| Status LED & LCD Display |
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
|||||
| Parameters On The LCD Panel |
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time |
|||||
| MANAGEMENT | ||||||
| Communication Interface |
RS-232,USB,Parallel card(Optional), SNMP card(Optional), Relay card (Optional) | |||||
| ENVIRONMENT | ||||||
| Operating Temperature | 0℃~40℃ | |||||
| Storage Temperature | -25℃~55℃ | |||||
| Humidity Range | 0~95% (Non-condensing) | |||||
| Altitude | < 1500m | |||||
| Noise Level | <55dB | <58dB | ||||
| PHYSICAL | ||||||
| Dimension W×D×H (mm) |
250×597×655 | 250×502×616 | ||||
| Net Weight (kg) | 76 | 35 | 45 | 46 | ||
| STANDARDS | ||||||
| Noise Suppression | Complies with EN62040-2 | |||||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||||
| IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||||